BASLER DECS-250E Digital Excitation Control System
The DECS-250E Digital Excitation Control System provides accurate and
reliable regulation, control, and protection for synchronous motors or
generators. Three DECS-250E models can supply a maximum of 50 Adc, 100
Adc, or 200 Adc of excitation current in a static or rotary exciter application. All
DECS-250E components are housed in a compact enclosure which makes for
a simple and cost-effective installation for a wide variety of applications
• Precise excitation control for synchronous generator or synchronous
motor applications.
• True RMS sensing, single-phase or three-phase voltage and current.
• Full generator or motor metering capabilities.
• Automatic Voltage Regulation / Field Current Regulation / Field Voltage
Regulation, Power Factor and var modes of operation.
• Integrated generator protection (27/59, 81O/U, 32R, 40Q), 59F, 51F, Field
Short Circuit, and 25 Sync Check.
• Load sharing over Ethernet.
• Auto tuning feature with two PID stability groups.
• Configurable protection.
• Conformal coating is applied to certain internal circuitry for additional
protection and reliability.
• Overexcitation limiting (with temperature compensation).
• Underexcitation limiting.
• Stator current limiting (with temperature compensation).
• Var limiting.
• Underfrequency limiting or V/Hz limiting.
• Trending, oscillography, and sequence of events recording.
• Ten programmable contact inputs.
• Nine programmable contact outputs.
• I/O expansion module compatibility.
- AEM-2020 Analog Expansion Module.
- CEM-2020 Contact Expansion Module.
• Single- or three-phase power input.
• Automatic synchronizer option.
• Compact enclosure.
• Reduce your setup time with Basler’s intuitive BESTCOMSPlus®
software that simplifies complex setup with simple drag-and-drop
programmable logic, visual real-time strip chart capabilities, and
cutting edge auto PID selection capabilities.
• The auto tuning function automatically establishes optimum PID
and gain settings, taking the guesswork out of system setup,
reducing commissioning time and cost while maximizing overall
system performance.
• The Offline Simulator in BESTlogic™Plus helps test and
troubleshoot logic without expensive hardware.
• A 50, 100, 200 ampere positive forcing rectifier bridge can be
selected to provide optimum response to the generator main field
Control Power Supply Input
Style LXXXXXXX
Voltage Range: 18 to 30 Vdc
Burden: 30 W*, 110 W
Style CXXXXXXX
DC Voltage Range: 90 to 150 Vdc
DC Burden: 30 W*, 100 W
AC Voltage Range: 90 to 132 Vac
AC Burden: 40 VA*, 150 VA
* With 50 Adc excitation current (style XXXXXXXA)
AC Operating Voltage and DC Output Power
120 Vac, 1-phase input: 63 Vdc output
80 Vac, 3-phase input: 63 Vdc output
240 Vac, 1-phase input: 125 Vdc output
160 Vac, 3-phase input: 125 Vdc output
320 Vac, 3-phase input: 250 Vdc output
Full Load Continuous
Current with Positive Forcing: 50, 100, or 200 Adc†
(style selectable)
† With 1-phase operating power input, 200 Adc styles
are de-rated to 133 Adc output.
10-Second Forcing: 1.44 x rated Adc
Power Input Frequency: 50/60 Hz
Generator Current Sensing
Configuration: 1-phase or 3-phase with separate
input for cross current
compensation
Current Ranges: 1 Aac or 5 Aac nominal
Frequency: 50/60 Hz Nominal
Burden: < 1 VA
Generator and Bus Voltage Sensing
Configuration: 1-phase or 3-phase
Voltage Ranges: 100/120 Vac ±10%
200/240 Vac ±10%
400/480 Vac ±10%
600 Vac ±10%
Frequency: 50/60 Hz Nominal
Burden: < 1 VA per phase
Inputs and Outputs
Contact Inputs: 10 programmable inputs
(dry contacts)
Auxiliary Input: Connection available in
4 to 20 mA or ±10 Vdc input
Output Contacts: 9 programmable form A
contacts and one form C for
watchdog function
Rating: Make, break, and carry 7 A
resistive @ 24/48/125 Vdc
(120/240 Vac).
Communication
USB: USB type B
RS-232: RS-232, 9 pin, sub D for
optional external autotracking
RS-485: Modbus® RTU protocol
CAN bus: One port for ECU communications
One port for expansion modules
Ethernet: 100base-T Modbus TCP protocol
for unit-to-unit communication
Expansion Port: Optional PROFIBUS protocol
Agency/Certifications
UL 6200:2019 recognized, UKCA, CE EMC, LVD, and
RoHS II compliant, China RoHS Compliant
Environmental
Operating Temp: -20°C to 60°C (-4°F to 140°F)
Storage Temp: -20°C to 75°C (-4°F to 167°F)
Humidity: IEC 60068-2-38
Ingress Protection: IP20 (NEMA1 cabinets available)
Shock: 15 G in three perpendicular planes
Vibration: IEC 60255-21-1, 3 hours per
plane, 3-25 Hz, 1.5 mm
displacement, 25-2,000 Hz, 5 G
acceleration, sweep rate 0.45
octaves per min.
Physical
Weight: 55.5 lb (25.2 kg)
Dimensions (WxHxD):
22.2 x 24.8 x 9.0 inches
(565 x 629 x 228 mm)
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.