and are available as standard also in the
REB500 functionality.
Directional sensitive earth fault protection
for grounded systems
A sensitive directional ground fault function
based on the measurement of neutral current
and voltage is provided for the detection of
high-resistance ground faults in solidly or lowresistance
grounded systems. The scheme
operates either in a permissive or blocking
mode and can be used in conjunction with an
inverse time earth fault overcurrent function.
In both cases the neutral current and voltage
can be derived either externally or internally.
This function works either with the same communication
channel as the distance protection
scheme or with an independent channel.
Directional sensitive earth fault protection
for ungrounded or compensated systems
The sensitive earth fault protection function for
ungrounded systems and compensated systems
with Petersen coils can be set for either
forwards or reverse measurement. The characteristic
angle is set to ±90°
(U0 · I0 · sin ) in ungrounded systems and to
0° or 180° (U0 · I0 · cos ) for systems with
Petersen coils. The neutral current is always
used for measurement in the case of systems
with Petersen coils, but in ungrounded systems
its use is determined by the value of the
capacitive current and measurement is performed
by a measuring CT to achieve the
required sensitivity. To perform this function
the BU03 with 3I, 1MT and 5U is required.
Definite time over- and undercurrent protection
This function is used as Main 2 or as back-up
function respectively for line, transformer or
bus-tie bays. This function can be activated in
the phase- and/or the neutral current circuit.
Inverse time overcurrent protection
The operating time of the inverse time overcurrent
function reduces as the fault current
increases and it can therefore achieve shorter
operating times for fault locations closer to the
source. Four different characteristics according
to British Standard 142 designated normal
inverse, very inverse, extremely inverse and
long time inverse but with an extended setting
range are provided. The function can be configured
for single phase measurement or a
combined three-phase measurement with
detection of the highest phase current.
Inverse time earth fault overcurrent protection
The inverse time earth fault overcurrent function
monitors the neutral current of the system.
Four different characteristics according
to British Standard 142 designated normal
inverse, very inverse, extremely inverse and
long time inverse but with an extended setting
range are provided.
Directional overcurrent definite / inverse
time protection
The directional overcurrent definite time function
is available either with inverse time or definite
time overcurrent characteristic. This
function comprises a voltage memory for
faults close to the relay location. The function
response after the memory time has elapsed
can be selected (trip or block).
Definite time over- and undervoltage protection
This function works with a definite time delay
with either single or three-phase measurement.
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.