system.
The flexibility of the system enables all configurations
of busbars from single busbars to
quadruple busbars with transfer buses, ring
busbars and 1½ breaker schemes to be protected.
In 1½ breaker schemes the busbars and the
entire diameters, including Stub/T-Zone can
be protected. An integrated tripping scheme
allows to save external logics as well as wiring.
The capacity is sufficient for up to 60 feeders
(bay units) and a total of 32 busbar zones.
The numerical busbar protection REB500
detects all phase and earth faults in solidly
grounded and resistive-grounded power systems
and phase faults in ungrounded systems
and systems with Petersen coils.
The main CTs supplying the currents to the
busbar protection have to fulfil only modest
performance requirements (see page 18). The
protection operates discriminatively for all
faults inside the zone of protection and
remains reliably stable for all faults outside the
zone of protection.
REB500sys
The REB500sys is foreseen in MV, HV and
EHV substations with nominal frequencies of
16.7, 50 Hz or 60 Hz to protect the busbars
and their feeders. The bay protection functions
included in REB500sys are used as
Main 2 / Group 1 - or back-up protection.
The system REB500sys is foreseen for all single
or double busbar configurations (Line variants
L-V1 to L-V7 and Transformer variant TV1
to T-V4). In 1½ breaker configurations,
variant L-V5 can be used for the bay level
functions autoreclosure and synchrocheck.
The capacity is sufficient for up to 60 feeders
(bay units) and a total of 32 busbar zones.
The REB500sys detects all bus faults in solidly
and low resistive-grounded power systems,
all kind of phase faults in ungrounded
and compensated power systems as well as
feeder faults in solidly, low resistive-grounded,
compensated and ungrounded power systems.
The protection operates selectively for all
faults inside the zone of protection and
remains reliably stable for all faults outside the
zone of protection.
REB500sys is perfectly suited for retrofit concepts
and stepwise upgrades. The bay unit is
used as a stand-alone unit for bay protection
functions (e.g. line protection, autoreclosure
and synchrocheck or 2- and 3 winding transformer
protection or autonomous T-zone protection).
The central unit can be added at a
later stage for full busbar and breaker failure
protection functionality.
data are transferred at regular intervals
from the bay units to the central processing
unit via the process bus.
Every bay unit has 20 binary inputs and 16
relay outputs. The binary I/O module detects
and processes the positions of isolators and
couplers, blocking signals, starting signals,
external resetting signals, etc. The binary
input channels operate according to a patented
pulse modulation principle in a nominal
range of 48 to 250 V DC. The PC-based HMI
program provides settings for the threshold
voltage of the binary inputs. All the binary output
channels are equipped with fast operating
relays and can be used for either signaling or
tripping purposes (see contact data in Table
8).
A software logic enables the input and output
channels to be assigned to the various functions.
A time stamp is attached to all the data
such as currents, voltages, binary inputs,
events and diagnostic information acquired by
a bay unit.
Where more binary and analog inputs are
needed, several bay units can be combined to
form a feeder/bus coupler bay (e.g. a bus coupler
bay with CTs on both sides of the bus-tie
breaker requires two bay units).
The bay unit is provided with local intelligence
and performs local protection (e.g. breaker
failure, end fault, breaker pole discrepancy),
bay protection (Main 2 or back-up bay protections)
as well as the event and disturbance
recording.
High-speed distance protection
• Overcurrent or underimpedance starters
with polygonal characteristic
• Five distance zones (polygon for forwards
and reverse measurement)
• Load-compensated measurement
• Definite time overcurrent back-up protection
(short-zone protection)
• System logic
- switch-onto-fault
- overreach zone
• Voltage transformer circuit supervision
• Power swing blocking function
• HF teleprotection. The carrier-aided
schemes include:
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.