data. This mid-value is then used by
the control program.
Analogue Output Modules
• 4 channel – 12 bit resolution
4–20mA TMR
Each of the three Triguard SC300E
processors sends voted output voltage
data to the analogue output modules.
The commands are received via
the bus system by the three
micro-controllers on each module
Pulse Input Analogue Output
Module (PIANO)
• 8 channel, 4 pulse input, 4 analogue
output TMR
The PIANO module contains fully
triplicated circuits. Each pulse input
path receives input pulses, a value
equivalent to the number of teeth on
a gear wheel for example, and
accumulates this data to an accuracy
of +_0.01% over 20Hz to 20KHz.
Output values to 12 bit resolution can
provide voted and validated data to
field devices for control (see analogue
output module for output circuit
operation).
Communications Module
A four channel serial communications
module is always fitted to a Triguard
SC300E TMR system to allow
communications to the engineering
workstation and is installed in I/O slot
number 10 of the main chassis. All
four channels operate RS232423 up
to 19.2 kbits/sec and all four
communication ports are fully isolated.
The four channel communications
module is directly addressed by the
three Triguard SC300E processors and
contains a micro-computer that
controls the four programmable
multi-protocol ports. Data received
from the three processors is voted
2oo3 providing correct data for
onward transmission.
High speed network
connectivity feature (to be
released)
Triguard may be interfaced to standard
communications networks such as
Ethernet/TCP/IP using approved
gateway products.
DCS connectivity includes:
• Yokogawa Electric, Elsag-Bailey,
Fisher Rosemount, ABB, Honeywell
and Foxboro
Hot Repair Facility
A quick repair procedure, once any
fault is revealed, is important in the
total fault tolerant product strategy.
The hot repair facility achieves a quick
and easy repair by the user and this is
done bumplessly without interrupting
the normal operation of the system
and process.
The operating system, RTTS, routinely
executes a hot repair task, checking
and validating that all configuration
data is correct, eg. correct I/O
module, on-line/off-line hot repair
functions.
All I/O modules can be programmed
for a hot repair facility. A wrong or
faulty module in an allocated hot
repair I/O slot will not be accepted.
Hot repair slots are selected to be
next to the system I/O resident
module.
There are three ways to replace an
on-line I/O module:
• Module with no additional hot
repair slot – single slot hot repair
• Module has an unpopulated hot
repair partner slot – manual hot
repair
• Module with a populated hot repair
partner slot – hot repair
Field Termination Cards
The types of termination cards
available:
• 16 channel – digital input
• 32 channel – digital input
• 16 channel – digital output
• 16 channel – analogue input
• 4 channel – analogue output
• 16 channel – digital output with line
monitoring
• 4 channel – pulse input
DIN rail mounted termination cards
for field wiring can be supplied as an
easy to fit method to route field cables
to the Triguard SC300E system I/O
modules, and distribute field wetting
current to each I/O point.
A termination card has an associated
system cable fitted with DIN
connectors to provide the plug and
socket arrangement. Cable lengths can
be specified to suit the application.
Alternative cables with Elco
connectors or free wires at the field
end are available for third party
marshalling systems.
Power and fusing for the field circuits
are standard. Options are available to
suit all field configurations.
System cables from the Triguard
SC300E are also available with free
wire ends so that the system may
connect to a separate cable
marshalling and power/fusing system.
Cabinet Layouts
Optional cabinets to house the
Triguard SC300E TMR control system
are industry standard 19” rack
mounted configurations with a width
of 600mm and a depth of 800mm. The
layouts shown are based on a standard
2000mm high cabinets, and provide
front and rear access. Front access
only configurations are available.
System Structure
A major benefit of the Triguard
SC300E system is that it can be as
small as one chassis or as large as 15,
All new products and surplus products of the industrial intelligence industry, as well as the discontinued products of the original manufacturers. We are not an authorized distributor or representative of any of the above manufacturers (except for brand authorization). The trademarks, brand names and brands appearing in this agreement are the property of their respective manufacturers.
COPYRIGHT© 2003-2025 Copyrighted
Phone(WeChat/Whatsapp)
+086-181 4410 0983
No 1134 Jimei North Road,
Hong Kong Office:
Guan Tang District, Hong Kong,